Programming and Parameters

3-5

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual

Publication 22B-UM001H-EN-E

Display Group

(continued)

d012 [Control Source]

Related Parameter(s):

P036

,

P038

,

A051

-

A054

Displays the active source of the Start Command and Speed Command which are normally defined
by the settings of

P036

[Start Source] and

P038

[Speed Reference] but may be overridden by digital

inputs. Refer to the flowcharts on pages

1-23

and

1-24

for details.

Values

Default:

Read Only

Min/Max:

0/9

Display:

1

Start Command

Digit 0

0 = Keypad
1 = 3-Wire
2 = 2-Wire
3 = 2-Wire Level Sensitive
4 = 2-Wire High Speed
5 = RS485 (DSI) Port
9 = Jog

Speed Command

Digit 1

0 = Drive Potentiometer
1 =

A069

[Internal Freq]

2 = 0-10V Input/Remote Potentiometer
3 = 4-20mA Input
4 =

A070

-

A077

[Preset Freq x]

(

A051

-

A053

[Digital Inx Sel] must be set to 4)

5 = RS485 (DSI) Port
6 = StepLogic Control (Parameters

A140

-

A147

)

7 = Anlg In Mult
8 = PID
9 = Jog Freq

Reserved

Digit 2

Reserved

Digit 3

d013 [Contrl In Status]

Related Parameter(s):

d002

,

P034

,

P035

Status of the control terminal block control inputs.
Important: Actual control commands may come from a source other than the control terminal block.

Values

Default:

Read Only

Min/Max:

0/1

Display:

1

1 = Input Present, 0 = Input Not Present

Start / Run FWD Input (I/O Terminal 02)

Bit 0

Direction / Run REV Input (I/O Terminal 03)

Bit 1

Stop Input

(1)

(I/O Terminal 01)

Bit 2

(1)

The stop input must be present in order to start the drive.
When this bit is a 1 the drive can be started.
When this bit is a 0 the drive will stop.

Dynamic Brake Transistor On

Bit 3