Programming and Parameters

3-19

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual

Publication 22B-UM001H-EN-E

A058,
A061
Options
(Cont.)

18 “Above PF Ang”

Power Factor angle has exceeded the value set in

A059

or

A062

[Opto Outx Level].

Use A059 or A062 to set threshold.

19 “Anlg In Loss”

Analog input loss has occurred. Program

A122

[Analog In

Loss] for desired action when input loss occurs.

20 “ParamControl”

Prior to FRN 4.01, this option enables the output to be
controlled over network communications by writing to

A059

or

A062

[Opto Outx Level]. (0 = Off, 1 = On.)

With FRN 4.01 and later:
Setting this option for A058 means the logic command word
bit 6 has full control of A059.
Setting this option for A059 means the logic command word
bit 7 has full control of A062.
See

Writing (06) Logic Command Data on page C-4

.

21 “NonRec Fault”

Value set in

A092

[Auto Rstrt Tries] is exceeded.

A092

[Auto Rstrt Tries] in not enabled.

A Non-resettable fault has occurred.

22 “EM Brk Cntrl”

EM brake is energized. Program

A160

[EM Brk Off Delay] and

A161

[EM Brk On Delay] for desired action.

23 “Above Fcmd”

The current commanded frequency exceeds the value set in

A059

or

A062

[Opto Outx Level].

24 “MsgControl”

With FRN 4.01 and later:
Enables the output to be controlled over the network
communications by writing to

A059

or

A062

[Opto Outx

Level]. (0 = Off, 1 = On.)

A059 [Opto Out1 Level]

Related Parameter(s):

A058

,

A061

A062 [Opto Out2 Level]

32 bit parameter.

Determines the on/off point for the opto outputs when

A058

or

A061

[Opto Outx Sel] is set to option 6,

7, 8, 10, 16, 17, 18 or 20.
With FRN 4.01 and later, when the value of A058 is set to 20, the logic command word bit 6 has full
control of A059 and when the value of A061 is set to 20, bit 7 has full control of A062.

Values

Default:

0.0

Min/Max:

0.0/9999

Display:

0.1

32

A058 & A061 Setting

A059 & A062 Min/Max

6
7
8
10
16
17
18
20
23

0/400 Hz
0/180%
0/815 Volts
0/100%
0.1/9999 Secs
1/9999 Counts
1/180 degs
0/1
0/400 Hz

22B-UM001.book Page 19 Wednesday, January 22, 2014 11:04 AM