3-12

Programming and Parameters

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual
Publication 22B-UM001H-EN-E

Basic Program Group

(continued)

P038 [Speed Reference]

Related Parameter(s):

d001

,

d002

,

d012

,

d020

,

d021

,

P039

,

P040

,

A051

-

A054

,

A069

,

A070

-

A077

,

A110

-

A113

,

A123

,

A132

,

A140

-

A147

,

A150

-

A157

Sets the source of the speed reference to the drive.
The drive speed command can be obtained from a number of different sources. The source is
normally determined by

P038

[Speed Reference]. However, when

A051

-

A054

[Digital Inx Sel] is set

to option 2, 4, 5, 6, 11, 12, 13, 14, 15 and the digital input is active, or if

A132

[PID Ref Sel] is not set

to option 0, the speed reference commanded by

P038

[Speed Reference] will be overridden. Refer to

the flowchart on

page 1-23

for more information on speed reference control priority.

Options

0 “Drive Pot” (Default)

Frequency command from the potentiometer on the integral
keypad.
Important: This option is not available with IP66, NEMA/UL
Type 4X rated drives. Internal frequency command comes
from

A069

[Internal Freq].

1 “InternalFreq”

(IP66, NEMA/UL Type
4X Default)

Internal frequency command from

A069

[Internal Freq]. Must

be set when using MOP function.

2 “0-10V Input”

External frequency command from the 0-10V or ±10V analog
input or remote potentiometer.

3 “4-20mA Input”

External frequency command from the 4-20mA analog input.

4 “Preset Freq”

External frequency command as defined by

A070

-

A077

[Preset Freq x] when

A051

-

A054

[Digital Inx Sel] are

programmed as “Preset Frequencies” and the digital inputs
are active.

5 “Comm Port”

External frequency command from the communications port.
Refer to Appendix C for details.

6 “Stp Logic”

External frequency command as defined by

A070

-

A077

[Preset Freq x] and

A140

-

A147

[Stp Logic x].

7 “Anlg In Mult”

External frequency command as defined by the product of the
analog inputs (shown in

d020

[Analog In 0-10V] and

d021

[Analog In 4-20mA]).
[Analog In 0-10V]

×

[Analog In 4-20mA] = Speed Command

Example: 100%

×

50% = 50%

P039 [Accel Time 1]

Related Parameter(s):

P038

,

P040

,

A051

-

A054

,

A067

,

A070

-

A077

,

A140

-

A147

Sets the rate of acceleration for all speed increases.

Values

Default:

10.0 Secs

Min/Max:

0.0/600.0 Secs

Display:

0.1 Secs

Maximum Freq

Accel Time

Accel Rate

=

Speed

0

Time

P035 [Maximum Freq]

P039 or A067
[Accel Time x]

P040 or A068

[Decel Time x]

0

Acceler

ation

Deceler

ation

22B-UM001.book Page 12 Wednesday, January 22, 2014 11:04 AM

Advertising