StepLogic™, Basic Logic and Timer/Counter Functions

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual
Publication 22B-UM001H-EN-E

Counter Function

Digital inputs and outputs control the counter function and are
configured with parameters A051-A054 [Digital Inx Sel] set to 19
“Counter In” and 21 “Reset Counter”.

Digital outputs (relay and opto type) define a preset level and indicate
when the level is reached. Level parameters A056 [Relay Out Level],
A059 [Opto Out1 Level] and A062 [Opto Out2 Level] are used to set the
desired count value.

Parameters A055 [Relay Out Sel], A058 [Opto Out1 Sel] and A061
[Opto Out2 Sel] are set to 17 “Counter Out” which causes the output to
change state when the level is reached.

Example

A photo eye is used to count packages on a conveyor line.

An accumulator holds the packages until 5 are collected.

A diverter arm redirects the group of 5 packages to a bundling area.

The diverter arm returns to its original position and triggers a limit
switch that resets the counter.

Parameters are set to the following options:

A051 [Digital In1 Sel] set to 19 to select “Counter In”

A052 [Digital In2 Sel] set to 21 to select “Reset Counter”

A055 [Relay Out Sel] set to 17 to select “Counter Out”

A056 [Relay Out Level] set to 5.0 (counts)