3-14

Programming and Parameters

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual
Publication 22B-UM001H-EN-E

Advanced Program Group

A051 [Digital In1 Sel]

(I/O Terminal 05)

A052 [Digital In2 Sel]

(I/O Terminal 06)

A053 [Digital In3 Sel]

(I/O Terminal 07)

A054 [Digital In4 Sel]

(I/O Terminal 08)

Related Parameter(s):

d012

,

d014

,

P038

,

P039

,

P040

,

A067

,

A068

,

A070

-

A077

,

A078

,

A079

,

A118

,

A140

-

A147

Selects the function for the digital inputs. Refer to the flowchart on

page 1-23

for more information on

speed reference control priority.

Options

0 “Not Used”

Terminal has no function but can be read over network
communications via

d014

[Dig In Status].

1 “Acc & Dec 2”

When active,

A067

[Accel Time 2] and

A068

[Decel Time

2] are used for all ramp rates except Jog.

Can only be tied to one input.

Refer to the flowchart on

page 1-24

for more information on

Accel/Decel selection.

2 “Jog”

When input is present, drive accelerates according to the
value set in

A079

[Jog Accel/Decel] and ramps to the

value set in

A078

[Jog Frequency].

When input is removed, drive ramps to a stop according to
the value set in

A079

[Jog Accel/Decel].

A valid “Start” command will override this input.

3 “Aux Fault”

When enabled, an F2

Auxiliary Input

fault will occur when the

input is removed.

4 “Preset Freq”

(A051 & A052 Default)

Refer to

A070

-

A077

[Preset Freq x].

Important: Digital Inputs have priority for frequency control
when programmed as Preset Speed and are active. Refer to
the flowchart on

page 1-23

for more information on speed

reference control priority.

5 “Local”

(A053 Default)

When active, sets integral keypad as start source and
potentiometer on the integral keypad as speed source.
Important: Speed source for IP66, NEMA/UL Type 4X rated
drives comes from

A069

[Internal Freq].

6 “Comm Port”

When active, sets communications device as default start/
speed command source.

Can only be tied to one input.

7 “Clear Fault”

When active, clears an active fault.

8 “RampStop,CF”

Causes drive to immediately ramp to a stop regardless of how

P037

[Stop Mode] is set.

9 “CoastStop,CF”

Causes drive to immediately coast to a stop regardless of
how

P037

[Stop Mode] is set.

10 “DCInjStop,CF”

Causes drive to immediately begin a DC Injection stop
regardless of how

P037

[Stop Mode] is set.

11 “Jog Forward”

(A054 Default)

Drive accelerates to

A078

[Jog Frequency] according to

A079

[Jog Accel/Decel] and ramps to stop when input becomes
inactive. A valid start will override this command.

12 “Jog Reverse”

Drive accelerates to

A078

[Jog Frequency] according to

A079

[Jog Accel/Decel] and ramps to stop when input becomes
inactive. A valid start will override this command.

Stop drive before changing this parameter.