3-34

Programming and Parameters

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual
Publication 22B-UM001H-EN-E

Advanced Program Group

(continued)

A113 [Anlg In4-20mA Hi]

Related Parameter(s):

d021

,

P035

,

P038

Sets the analog input level that corresponds to

P035

[Maximum Freq] if a 4-20mA input is used by

P038

[Speed Reference].

Analog inversion can be accomplished by setting this value smaller than A112 [Anlg In4-20mA Lo].

Values

Default:

100.0%

Min/Max:

0.0/100.0%

Display:

0.1%

A114 [Slip Hertz @ FLA]

Related Parameter(s):

P033

Compensates for the inherent slip in an induction motor. This frequency is added to the commanded
output frequency based on motor current.

Values

Default:

2.0 Hz

Min/Max:

0.0/10.0 Hz

Display:

0.1 Hz

A115 [Process Time Lo]

Related Parameter(s):

d010

,

P034

Scales the time value when the drive is running at

P034

[Minimum Freq]. When set to a value other

than zero,

d010

[Process Display] indicates the duration of the process.

Values

Default:

0.00

Min/Max:

0.00/99.99

Display:

0.01

A116 [Process Time Hi]

Related Parameter(s):

d010

,

P035

Scales the time value when the drive is running at

P035

[Maximum Freq]. When set to a value other

than zero,

d010

[Process Display] indicates the duration of the process.

Values

Default:

0.00

Min/Max:

0.00/99.99

Display:

0.01

A117 [Bus Reg Mode]

Controls the operation of the drive voltage regulation, which is normally operational at decel or when
the bus voltage rises.
Refer to the Attention statement on page

P-3

for important information on bus regulation.

Options

0 “Disabled”

1 “Enabled” (Default)

A118 [Current Limit 2]

Related Parameter(s):

P033

,

A051

-

A054

,

A089

Maximum output current allowed before current limiting occurs. This parameter is only active if

A051

-

A054

[Digital Inx Sel] is set to 25 “Current Lmt2” and is active.

Values

Default:

Drive Rated Amps

×

1.5

Min/Max:

0.1/(Drive Rated Amps

×

1.8)

Display:

0.1 Amps