Fault indication, Manually clearing faults, Automatically clearing faults – Rockwell Automation 22B PowerFlex 40 FRN 1.xx - 6.xx User Manual

Page 94: Auto restart (reset/run)

Advertising
background image

4-2

Troubleshooting

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual
Publication 22B-UM001H-EN-E

Fault Indication

Manually Clearing Faults

Automatically Clearing Faults

Auto Restart (Reset/Run)

The Auto Restart feature provides the ability for the drive to
automatically perform a fault reset followed by a start attempt without
user or application intervention. This allows remote or “unattended”
operation. Only certain faults are allowed to be reset. Certain faults
(Type 2) that indicate possible drive component malfunction are not
resettable.

Caution should be used when enabling this feature, since the drive will
attempt to issue its own start command based on user selected programming.

Condition

Display

Drive is indicating a fault.
The integral keypad provides visual notification of a
fault condition by displaying the following.

Flashing fault number

Flashing fault indicator

Press the Escape key to regain control of the
integral keypad.

Step

Key(s)

1. Press Esc to acknowledge the fault. The fault information will be

removed so that you can use the integral keypad.
Access d007

[Fault 1 Code]

to view the most recent fault information.

2. Address the condition that caused the fault.

The cause must be corrected before the fault can be cleared.
See

Table 4.A

.

3. After corrective action has been taken, clear the fault by one of these

methods.

Press Stop if

P037

[Stop Mode] is set to a value between “0” and “3”.

Cycle drive power.

Set

A100

[Fault Clear] to “1” or “2”.

Cycle digital input if

A051

-

A054

[Digital Inx Sel] is set to option 7

“Clear Fault”.

Option / Step

Clear a Type 1 fault and restart the drive.
1. Set

A092

[Auto Rstrt Tries] to a value other than “0”.

2. Set

A093

[Auto Rstrt Delay] to a value other than “0”.

Clear an OverVoltage, UnderVoltage or Heatsink OvrTmp fault
without restarting the drive.
1. Set

A092

[Auto Rstrt Tries] to a value other than “0”.

2. Set

A093

[Auto Rstrt Delay] to “0”.

FAULT

VOLTS

AMPS

HERTZ

RUN

FWD

REV

PRGOGRAM