Installation/Wiring

1-21

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual

Publication 22B-UM001H-EN-E

3 Wire SNK Control -
Reversing

Internal Supply (SNK)

Opto Output (1 & 2)

A058

[Opto Out1 Sel]

determines
Opto-Output 1 (I/O
Terminal 17) operation.

A061

[Opto Out2 Sel]

determines
Opto-Output 2 (I/O
Terminal 18) operation.
When using
Opto-Output with an
inductive load such as
a relay, install a
recovery diode parallel
to the relay as shown,
to prevent damage to
the output.

Opto-Output 1

Analog Output

A065

[Analog Out Sel]

determines analog
output type and drive
conditions.
0-10V,
1k ohm minimum

0-20mA/4-20mA,
525 ohm maximum

A065

[Analog Out Sel] = 0 through 14

The Analog Output Select DIP Switch must be set to match the analog output
signal mode set in

A065

[Analog Out Sel].

Input/Output

Connection Example

Stop

Start

Direction

01

02

03

04

Common

+24V

CR

09

17

Each Opto-Output is rated
30V DC 50 mA (Non-inductive).

14

16

Common

+