4-6

Troubleshooting

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual
Publication 22B-UM001H-EN-E

Drive does not Start from Start or Run Inputs wired to the terminal block.

Drive does not Start from Integral Keypad.

Cause(s)

Indication

Corrective Action

Drive is Faulted

Flashing red status light

Clear fault.

Press Stop

Cycle power

Set

A100

[Fault Clear] to option 1

“Clear Faults”.

Cycle digital input if

A051

-

A054

[Digital Inx Sel] is set to option 7
“Clear Fault”.

Incorrect programming.

P036

[Start Source] is set to

option 0 “Keypad” or option 5
“RS485 (DSI) Port”.

A051

-

A054

[Digital Inx Sel] is

set to option 5 “Local” and the
input is active.

None

Check parameter settings.

Incorrect input wiring.
See

1-18

for wiring examples.

2 wire control requires Run
Forward, Run Reverse or Jog
input.

3 wire control requires Start and
Stop inputs

Stop input is always required.

None

Wire inputs correctly and/or install
jumper.

Incorrect Sink/Source DIP switch
setting.

None

Set switch to match wiring scheme.

Cause(s)

Indication

Corrective Action

Integral keypad is not enabled. Green LED above Start key is

not illuminated.

Set parameter

P036

[Start

Source] to option 0 “Keypad”.

Set parameter

A051

-

A054

[Digital Inx Sel] to option 5
“Local” and activate the input.

I/O Terminal 01 “Stop” input is
not present.

None

Wire inputs correctly and/or install
jumper.