3-38

Programming and Parameters

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual
Publication 22B-UM001H-EN-E

Advanced Program Group

(continued)

A130 [PID Trim Hi]

Sets the maximum positive value that is added to the speed reference when PID trim is used.

Values

Default:

60.0

Min/Max:

0.0/400.0

Display:

0.1

A131 [PID Trim Lo]

Sets the maximum positive value that is subtracted from the PID reference when PID trim is used.

Values

Default:

0.0

Min/Max:

0.0/400.0

Display:

0.1

A132 [PID Ref Sel]

Related Parameter(s):

P038

,

A122

Stop drive before changing this parameter.

Enables/disables PID mode and selects the source of the PID reference. Refer to

Appendix F

for

details.

Options

0 “PID Disabled”

(Default)

1 “PID Setpoint”

2 “0-10V Input”

3 “4-20mA Input”

4 “Comm Port”

5 “Setpnt, Trim”

6 “0-10V, Trim”

7 “4-20mA, Trim”

8 “Comm, Trim”

A133 [PID Feedback Sel]

Select the source of the PID feedback. Refer to

Appendix F

for details.

Options

0 “0-10V Input” (Default) The PID will not function with a bipolar input. Negative

voltages are treated as 0 volts.

1 “4-20mA Input”

2 “Comm Port”

A134 [PID Prop Gain]

Sets the value for the PID proportional component when the PID mode is enabled by A132 [PID Ref
Sel].

Values

Default:

0.01

Min/Max:

0.00/99.99

Display:

0.01