Programming and Parameters

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual
Publication 22B-UM001H-EN-E

Basic Program Group

(continued)

P036 [Start Source]

Related Parameter(s):

d012

,

P037

Stop drive before changing this parameter.

Sets the control scheme used to start the drive.
Refer to

Start and Speed Reference Control on page 1-23

for details about how other drive settings

can override the setting of this parameter.
Important: For all settings except option 3, the drive must receive a leading edge from the start input
for the drive to start after a stop input, loss of power or fault condition.

Options

0 “Keypad” (Default)

Integral keypad controls drive operation.

I/O Terminal 1 “Stop” = coast to stop.

When active, the Reverse key is also active unless
disabled by

A095

[Reverse Disable].

1 “3-Wire”

I/O Terminal 1 “Stop” = stop according to the value set in

P037

[Stop Mode].

2 “2-Wire”

I/O Terminal 1 “Stop” = coast to stop.

3 “2-W Lvl Sens”

Drive will restart after a “Stop” command when:

Stop is removed
and

Start is held active

4 “2-W Hi Speed”

Important: There is greater potential voltage on the output
terminals when using this option.

Outputs are kept in a ready-to-run state. The drive will
respond to a “Start” command within 10 ms.

I/O Terminal 1 “Stop” = coast to stop.

5 “Comm Port”

Remote communications. Refer to Appendix C for details.

I/O Terminal 1 “Stop” = coast to stop.

6 “Momt FWD/REV”

Drive will start after a momentary input from either the
Run FWD Input (I/O Terminal 02) or the Run REV Input (I/
O Terminal 03).

I/O Terminal 1 “Stop” = coast to stop.

!

ATTENTION:

Hazard of injury exists due to unintended operation.

When P036 [Start Source] is set to option 3, and the Run input is
maintained, the Run inputs do not need to be toggled after a Stop input for
the drive to run again. A Stop function is provided only when the Stop input
is active (open).