Programming and Parameters

3-9

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual

Publication 22B-UM001H-EN-E

Basic Program Group

P031 [Motor NP Volts]

Related Parameter(s):

d004

,

A084

,

A085

,

A086

,

A087

Stop drive before changing this parameter.

Set to the motor nameplate rated volts.

Values

Default:

Based on Drive Rating

Min/Max:

20/Drive Rated Volts

Display:

1 VAC

P032 [Motor NP Hertz]

Related Parameter(s):

A084

,

A085

,

A086

,

A087

,

A090

Stop drive before changing this parameter.

Set to the motor nameplate rated frequency.

Values

Default:

60 Hz

Min/Max:

15/400 Hz

Display:

1 Hz

P033 [Motor OL Current]

Related Parameter(s):

A055

,

A058

,

A061

,

A089

,

A090

,

A098

,

A114

,

A118

Set to the maximum allowable motor current.

The drive will fault on an F7

Motor Overload

if the value of this parameter is exceeded by 150% for 60

seconds.

Values

Default:

Based on Drive Rating

Min/Max:

0.0/(Drive Rated Amps

×

2)

Display:

0.1 Amps

P034 [Minimum Freq]

Related Parameter(s):

d001

,

d002

,

d013

,

P035

,

A085

,

A086

,

A087

,

A110

,

A112

Sets the lowest frequency the drive will output continuously.

Values

Default:

0.0 Hz

Min/Max:

0.0/400.0 Hz

Display:

0.1 Hz

P035 [Maximum Freq]

Related Parameter(s):

d001

,

d002

,

d013

,

P034

,

A065

,

A078

,

A085

,

A086

,

A087

,

A111

,

A113

Stop drive before changing this parameter.

Sets the highest frequency the drive will output.

Values

Default:

60 Hz

Min/Max:

0/400 Hz

Display:

1 Hz