RS485 (DSI) Protocol

PowerFlex 40 drives support the RS485 (DSI) protocol to allow efficient
operation with Rockwell Automation peripherals. In addition, some
Modbus functions are supported to allow simple networking. PowerFlex
40 drives can be multi-dropped on an RS485 network using Modbus
protocol in RTU mode.

For information regarding DeviceNet or other communication protocols,
refer to the appropriate user manual.

Network Wiring

Network wiring consists of a shielded 2-conductor cable that is
daisy-chained from node to node.

Figure C.1 Network Wiring Diagram

Controller

V/T2

T/L3

S/L2

R/L1

U/T1

W/T3

BR+ BR-

DC- DC+

Master

PowerFlex 40

Node 1

4

5

PowerFlex 40

Node 2

4

5

PowerFlex 40

Node "n"

4

5

TxRxD+

TxRxD-

TxRxD+

TxRxD-

TxRxD+

TxRxD-

120 ohm resistor

120 ohm resistor

FRONT

PIN 8

PIN 1

NOTE: The shield should be grounded at ONLY ONE location.

Shield

Shield

Shield

TxRxD+

TxRxD-

RS485

(DSI)

AK-U0-RJ45-TB2P

RS485

(DSI)

TxRxD+

TxRxD-

V/T2

T/L3

S/L2

R/L1

U/T1

W/T3

BR+ BR-

DC- DC+

01 02 03 04 05

11 12 13 14 15

06 07 08 09

16 17 18 19

01 02 03 04 05

11 12 13 14 15

06 07 08 09

16 17 18 19