F-4

PID Set Up

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual
Publication 22B-UM001H-EN-E

PID Reference and Feedback

Parameter A132 [PID Ref Sel] is used to enable the PID mode (A132 ¦ 0
“PID Disabled”) and to select the source of the PID Reference. If A132
[PID Ref Sel] is not set to 0 “PID Disabled”, PID can still be disabled by
select programmable digital input options (parameters

A051

-

A054

) such

as “Jog”, “Local” or “PID Disable”.

Table F.A A132 [PID Ref Sel] Options

A133 [PID Feedback Sel] is used to select the source of the PID
feedback.

Table F.B A133 [PID Feedback Sel] Options

Option

Description

0 “PID Disabled”

Disables the PID loop (default setting)

1 “PID Setpoint“

Selects Exclusive Control. A137 [PID Setpoint] will be used to
set the value of the PID Reference

2 “0-10V Input”

Selects Exclusive Control. Selects the 0-10V Input. Note that
the PID will not function with a bipolar analog input. It will
ignore any negative voltages and treat them like a zero.

3 “4-20mA Input”

Selects Exclusive Control. Selects the 4-20mA Input.

4 “Comm Port”

Selects Exclusive Control. The reference word from a
communication network (see

Appendix C

for details on the

reference word) such as Modbus RTU or DeviceNet becomes
the PID Reference. The value sent over the network is scaled
so that P035 [Maximum Freq] x 10 = 100% reference. For
example, with [Maximum Freq] = 60 Hz, a value of 600 sent
over the network would represent 100% reference.

5 “Setpnt, Trim”

Selects Trim Control. A137 [PID Setpoint] will be used to set
the value of the PID Reference.

6 “0-10V, Trim”

Selects Trim Control. Selects the 0-10V Input. Note that the
PID will not function with a bipolar analog input. It will ignore
any negative voltages and treat them like a zero.

7 “4-20mA, Trim”

Selects Trim Control. Selects the 4-20mA Input.

8 “Comm, Trim”

Selects Trim Control. The reference word from a
communication network (see

Appendix C

for details on the

reference word) such as Modbus RTU or DeviceNet becomes
the PID Reference. The value sent over the network is scaled
so that P035 [Maximum Freq] x 10 = 100% reference. For
example, with [Maximum Freq] = 60 Hz, a value of 600 sent
over the network would represent 100% reference.

Option

Description

0 “0-10V Input”

Selects the 0-10V Input (default setting). Note that the PID will
not function with a bipolar analog input. It will ignore any
negative voltages and treat them like a zero.

1 “4-20mA Input“

Selects the 4-20mA Input.

2 “Comm Port”

The reference word from a communication network (see
Appendix C of the PowerFlex 40 User Manual for details on the
reference word) such as Modbus RTU or DeviceNet becomes
the PID Feedback. The value sent over the network is scaled
so that P035 [Maximum Freq] x 10 = 100% Feedback. For
example, with [Maximum Freq] = 60 Hz, a value of 600 sent
over the network would represent 100% Feedback.

22B-UM001.book Page 4 Wednesday, January 22, 2014 11:04 AM