Rockwell Automation 22B PowerFlex 40 FRN 1.xx - 6.xx User Manual

Page 104

Advertising
background image

A-4

Supplemental Drive Information

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual
Publication 22B-UM001H-EN-E

Category

Specification

Environment

Altitude:

1000 m (3300 ft) max. without derating

Maximum Surrounding Air
Temperature without derating:

IP20, NEMA/UL Type Open:
IP30, NEMA/UL Type 1:
Flange Mount:

IP66, NEMA/UL Type 4X:

–10 to 50° C (14 to 122° F)
–10 to 40° C (14 to 104° F)
Heatsink: –10 to 40° C (14 to 104° F)
Drive:

–10 to 50° C (14 to 122° F)

–10 to 40° C (14 to 104° F)

Cooling Method

Convection:
Fan:

0.4 kW (0.5 HP) drives
All other drive ratings and 0.4 kW (0.5 HP)
1-Phase drives with Integral “S Type” EMC Filter

Storage Temperature:

–40 to 85 degrees C (–40 to 185 degrees F)

Atmosphere:

Important: Drive must not be installed in an
area where the ambient atmosphere contains
volatile or corrosive gas, vapors or dust. If the
drive is not going to be installed for a period of
time, it must be stored in an area where it will not
be exposed to a corrosive atmosphere.

Relative Humidity:

0 to 95% non-condensing

Shock (operating):

15G peak for 11ms duration (±1.0ms)

Vibration (operating):

1G peak, 5 to 2000 Hz

Control

Carrier Frequency

2-16 kHz. Drive rating based on 4 kHz.

Frequency Accuracy

Digital Input:
Analog Input:

Analog Output:

Within ±0.05% of set output frequency.
Within 0.5% of maximum output frequency,
10-Bit resolution
±2% of full scale, 10-Bit resolution

Speed Regulation - Open Loop
with Slip Compensation:

±1% of base speed across a 60:1 speed range.

Stop Modes:

Multiple programmable stop modes including -
Ramp, Coast, DC-Brake, Ramp-to-Hold and
S Curve.

Accel/Decel:

Two independently programmable accel and
decel times. Each time may be programmed from
0 - 600 seconds in 0.1 second increments.

Intermittent Overload:

150% Overload capability for up to 1 minute
200% Overload capability for up to 3 seconds

Electronic Motor Overload
Protection:

Provides class 10 motor overload protection
according to NEC article 430 and motor
over-temperature protection according to NEC
article 430.126 (A) (2). UL 508C File 29572.

Electrical

Voltage Tolerance:

100-120V ±10%
200-240V ±10%
380-480V ±10%
460-600V ±10%

Frequency Tolerance:

48-63 Hz

Input Phases:

Three-phase input provides full rating. Single-phase
operation provides 35% rated current.

Displacement Power Factor:

0.98 across entire speed range

Maximum Short Circuit Rating:

100,000 Amps Symmetrical

Actual Short Circuit Rating:

Determined by AIC Rating of installed fuse/circuit
breaker

Transistor Type:

Insulated Gate Bipolar Transistor (IGBT)

22B-UM001.book Page 4 Wednesday, January 22, 2014 11:04 AM