Programming and Parameters

3-41

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual

Publication 22B-UM001H-EN-E

Digit 3: Step Settings
This digit defines what accel/decel profile the speed command will follow and the direction of the
command for the current step. In addition, if a relay or opto output (parameters A055, A058 and A061)
is set to 15 “StpLogic Out”, this parameter can control the status of that output.
Any StepLogic parameter can be programmed to control a relay or opto output, but you can not
control different outputs based on the condition of different StepLogic commands.

StepLogic Settings
The logic for each function is determined by the four digits for each StepLogic parameter. The
following is a listing of the available settings for each digit.
Refer to

Appendix E

for details.

Logic For Next Step

Digit 0

Logic to Jump to a Different Step

Digit 1

Different Step to Jump

Digit 2

Step Settings

Digit 3

Digit 3 Settings

Required

Setting

Accel/Decel

Param. Used

StepLogic

Output State

Commanded

Direction

0
1
2
3
4
5
6
7
8
9

A

b

Accel/Decel 1
Accel/Decel 1
Accel/Decel 1
Accel/Decel 1
Accel/Decel 1
Accel/Decel 1
Accel/Decel 2
Accel/Decel 2
Accel/Decel 2
Accel/Decel 2
Accel/Decel 2
Accel/Decel 2

Off
Off
Off
On
On
On
Off
Off
Off
On
On
On

FWD

REV

No Output

FWD

REV

No Output

FWD

REV

No Output

FWD

REV

No Output

Digit 2 Settings

Digit 1 and Digit 0 Settings

0 = Jump to Step 0
1 = Jump to Step 1
2 = Jump to Step 2
3 = Jump to Step 3
4 = Jump to Step 4
5 = Jump to Step 5
6 = Jump to Step 6
7 = Jump to Step 7
8 = End Program (Normal Stop)
9 = End Program (Coast to Stop)
A = End Program and Fault (F2)

0 = Skip Step (Jump Immediately)
1 = Step Based on [Stp Logic Time x]
2 = Step if “Logic In1” is Active
3 = Step if “Logic In2” is Active
4 = Step if “Logic In1” is Not Active
5 = Step if “Logic In2” is Not Active
6 = Step if either “Logic In1” or “Logic In2” is Active
7 = Step if both “Logic In1” and “Logic In2” is Active
8 = Step if neither “Logic In1” or “Logic In2” is Active
9 = Step if “Logic In1” is Active and “Logic In2” is Not Active
A = Step if “Logic In2” is Active and “Logic In1” is Not Active
b = Step after [Stp Logic Time x] and “Logic In1” is Active
C = Step after [Stp Logic Time x] and “Logic In2” is Active
d = Step after [Stp Logic Time x] and “Logic In1” is Not Active
E = Step after [Stp Logic Time x] and “Logic In2” is Not Active
F = Do Not Step/Ignore Digit 2 Settings