Programming and Parameters

3-39

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual

Publication 22B-UM001H-EN-E

Advanced Program Group

(continued)

A135 [PID Integ Time]

Sets the value for the PID integral component when the PID mode is enabled by A132 [PID Ref Sel].

Values

Default:

0.1 Secs

Min/Max:

0.0/999.9 Secs

Display:

0.1 Secs

A136 [PID Diff Rate]

Sets the value for the PID differential component when the PID mode is enabled by A132 [PID Ref
Sel].

Values

Default:

0.01 (1/Secs)

Min/Max:

0.00/99.99 (1/Secs)

Display:

0.01 (1/Secs)

A137 [PID Setpoint]

Provides an internal fixed value for process setpoint when the PID mode is enabled by A132 [PID Ref
Sel].

Values

Default:

0.0%

Min/Max:

0.0/100.0%

Display:

0.1%

A138 [PID Deadband]

Sets the lower limit of the PID output.

Values

Default:

0.0%

Min/Max:

0.0/10.0%

Display:

0.1%

A139 [PID Preload]

Sets the value used to preload the integral component on start or enable.

Values

Default:

0.0 Hz

Min/Max:

0.0/400.0 Hz

Display:

0.1 Hz