A065, A064, Et in – Rockwell Automation 22B PowerFlex 40 FRN 1.xx - 6.xx User Manual

Page 66: Advanced program group, Continued), A064 [opto out logic, A065 [analog out sel

Advertising
background image

3-20

Programming and Parameters

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual
Publication 22B-UM001H-EN-E

Advanced Program Group

(continued)

A064 [Opto Out Logic]

Determines the logic (Normally Open/NO or Normally Closed/NC) of the opto outputs.

Values

Default:

0

Min/Max:

0/3

Display:

1

A064 Option

Opto Out1 Logic

Opto Out2 Logic

0
1
2
3

NO (Normally Open)
NC (Normally Closed)
NO (Normally Open)
NC (Normally Closed)

NO (Normally Open)
NO (Normally Open)
NC (Normally Closed)
NC (Normally Closed)

A065 [Analog Out Sel]

Related Parameter(s):

P035

,

A066

Sets the analog output signal mode (0-10V, 0-20mA, or 4-20mA). The output is used to provide a
signal that is proportional to several drive conditions.

Values

Default:

0

Min/Max:

0/23

Display:

1

Option

Output
Range

Minimum Output
Value

Maximum Output Value
A066 [Analog Out High]

DIP Switch
Position

Related
Parameter

0 “OutFreq 0-10”

0-10V

0V = 0 Hz

P035 [Maximum Freq]

0-10V

d001

1 “OutCurr 0-10”

0-10V

0V = 0 Amps

200% Drive Rated Output Current 0-10V

d003

2 “OutVolt 0-10”

0-10V

0V = 0 Volts

120% Drive Rated Output Volts

0-10V

d004

3 “OutPowr 0-10”

0-10V

0V = 0 kW

200% Drive Rated Power

0-10V

d022

4 “TstData 0-10”

0-10V

0V = 0000

65535 (Hex FFFF)

0-10V

d019

5 “OutFreq 0-20”

0-20mA

0 mA = 0 Hz

P035 [Maximum Freq]

0-20mA

d001

6 “OutCurr 0-20”

0-20mA

0 mA = 0 Amps

200% Drive Rated Output Current 0-20mA

d003

7 “OutVolt 0-20”

0-20mA

0 mA = 0 Volts

120% Drive Rated Output Volts

0-20mA

d004

8 “OutPowr 0-20”

0-20mA

0 mA = 0 kW

200% Drive Rated Power

0-20mA

d022

9 “TstData 0-20”

0-20mA

0 mA = 0000

65535 (Hex FFFF)

0-20mA

d019

10 “OutFreq 4-20”

4-20mA

4 mA = 0 Hz

P035 [Maximum Freq]

0-20mA

d001

11 “OutCurr 4-20”

4-20mA

4 mA = 0 Amps

200% Drive Rated Output Current 0-20mA

d003

12 “OutVolt 4-20”

4-20mA

4 mA = 0 Volts

120% Drive Rated Output Volts

0-20mA

d004

13 “OutPowr 4-20” 4-20mA

4 mA = 0 kW

200% Drive Rated Power

0-20mA

d022

14 “TstData 4-20”

4-20mA

4 mA = 0000

65535 (Hex FFFF)

0-20mA

d019

15 “OutTorq 0-10”

0-10V

0V = 0 Amps

200% Drive Rated FLA

0-10V

d029

16 “OutTorq 0-20”

0-20 mA

0 mA = 0 Amps

200% Drive Rated FLA

0-20 mA

d029

17 “OutTorq 4-20”

4-20 mA

4 mA = 0 Amps

200% Drive Rated FLA

0-20 mA

d029

18 “Setpnt 0-10”

0-10V

0V = 0%

100.0% Setpoint Setting

0-10V

A109

19 “Setpnt 0-20”

0-20 mA

0 mA = 0%

100.0% Setpoint Setting

0-20 mA

A109

20 “Setpnt 4-20”

4-20 mA

4 mA = 0%

100.0% Setpoint Setting

0-20 mA

A109

21 “MinFreq 0-10”

0-10V

0V = Min. Freq

P035 [Maximum Freq]

0-10V

d001

22 “MinFreq 0-20”

0-20 mA

0 mA = Min. Freq P035 [Maximum Freq]

0-20 mA

d001

23 “MinFreq 4-20”

4-20 mA

4 mA = Min. Freq P035 [Maximum Freq]

0-20 mA

d001

22B-UM001.book Page 20 Wednesday, January 22, 2014 11:04 AM

Advertising