Input power conditioning – Rockwell Automation 22B PowerFlex 40 FRN 1.xx - 6.xx User Manual

Page 16

Advertising
background image

1-6

Installation/Wiring

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual
Publication 22B-UM001H-EN-E

Input Power Conditioning

The drive is suitable for direct connection to input power within the rated
voltage of the drive (see

Appendix A

). Listed in

Table 1.B

are certain

input power conditions which may cause component damage or
reduction in product life. If any of the conditions exist, as described in

Table 1.B

, install one of the devices listed under the heading Corrective

Action on the line side of the drive.

Important: Only one device per branch circuit is required. It should be

mounted closest to the branch and sized to handle the total
current of the branch circuit.

Table 1.B Input Power Conditions

Input Power Condition

Corrective Action

Low Line Impedance (less than 1% line reactance)

Install Line Reactor

(2)

or Isolation Transformer

or Bus Inductor – 5.5 & 11 kW
(7.5 & 15 HP) drives only

(2)

Refer to

Appendix B

for accessory ordering information.

Greater than 120 kVA supply transformer

Line has power factor correction capacitors

Install Line Reactor

or Isolation Transformer

Line has frequent power interruptions

Line has intermittent noise spikes in excess of
6000V (lightning)

Phase to ground voltage exceeds 125% of normal
line to line voltage

Remove MOV jumper to ground.

or Install Isolation Transformer
with grounded secondary if
necessary.

Ungrounded distribution system

240V open delta configuration (stinger leg)

(1)

(1)

For drives applied on an open delta with a middle phase grounded neutral system, the
phase opposite the phase that is tapped in the middle to the neutral or earth is
referred to as the “stinger leg,” “high leg,” “red leg,” etc. This leg should be identified
throughout the system with red or orange tape on the wire at each connection point.
The stinger leg should be connected to the center Phase B on the reactor. Refer to

Table B.D

for specific line reactor part numbers.

Install Line Reactor