Steplogic using timed steps, Steplogic sequence – Rockwell Automation 22B PowerFlex 40 FRN 1.xx - 6.xx User Manual

Page 138

Advertising
background image

E-2

StepLogic™, Basic Logic and Timer/Counter Functions

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual
Publication 22B-UM001H-EN-E

StepLogic Using Timed Steps

To activate this function, set parameter P038 [Speed Reference] to 6 “Stp
Logic”. Three parameters are used to configure the logic, speed
reference and time for each step.

Logic is defined using parameters A140-A147 [Stp Logic x].

Preset Speeds are set with parameters A070-A077 [Preset Freq x].

Time of operation for each step is set with parameters A150-A157
[Stp Logic Time x].

The direction of motor rotation can be forward or reverse.

Figure E.1 Using Timed Steps

StepLogic Sequence

Sequence begins with a valid start command.

A normal sequence begins with Step 0 and transition to the next step
when the corresponding StepLogic time has expired.

Step 7 is followed by Step 0

Sequence repeats until a stop is issued or a fault condition occurs.

Time

0

Forward

Reverse

Step 0

Step 1

Step 2

Step 3 Step 4 Step 5 Step 6

Step 7

22B-UM001.book Page 2 Wednesday, January 22, 2014 11:04 AM