A066, Advanced program group, Continued) – Rockwell Automation 22B PowerFlex 40 FRN 1.xx - 6.xx User Manual

Page 67: A066 [analog out high, A067 [accel time 2

Advertising
background image

Programming and Parameters

3-21

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual

Publication 22B-UM001H-EN-E

Advanced Program Group

(continued)

A066 [Analog Out High]

Related Parameter(s):

A065

Scales the Maximum Output Value for the

A065

[Analog Out Sel] source setting.

Examples:

Values

Default:

100%

Min/Max:

0/800%

Display:

1%

A066 Setting

A065 Setting

A065 Max. Output Value

50%

1 “OutCurr 0-10”

5V for 200% Drive Rated Output Current

90%

8 “OutPowr 0-20”

18mA for 200% Drive Rated Power

A067 [Accel Time 2]

Related Parameter(s):

P039

,

A051

-

A054

,

A070

-

A077

,

A140

-

A147

When active, sets the rate of acceleration for all speed increases except jog. Refer to the flowchart on
page

1-24

for details.

Values

Default:

20.0 Secs

Min/Max:

0.0/600.0 Secs

Display:

0.1 Secs

Maximum Freq

Accel Time

Accel Rate

=

Speed

0

Time

P035 [Maximum Freq]

P039 or A067
[Accel Time x]

P040 or A068

[Decel Time x]

0

Acceler

ation

Deceler

ation

22B-UM001.book Page 21 Wednesday, January 22, 2014 11:04 AM