Programming and Parameters

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual
Publication 22B-UM001H-EN-E

Advanced Program Group

(continued)

A164 [Comm Write Mode]

Determines whether parameter changes made over communication port are saved and stored in
Non-Volatile Storage (NVS) or RAM only. If they are stored in RAM, the values will be lost at
power-down.

Options

0 “Save” (Default)

1 “RAM Only”

!

ATTENTION:

Risk of equipment damage exists. If a controller is programmed to

write parameter data to Non-Volatile Storage (NVS) frequently, the NVS will quickly
exceed its life cycle and cause the drive to malfunction. Do not create a program that
frequently uses configurable outputs to write parameter data to NVS unless A164
[Comm Write Mode] is set to option 1.

A165 [Anlg Loss Delay]

Related Parameter(s):

A122

Sets the length of time after power-up during which the drive will not detect an analog signal loss. The
drive response to an analog signal loss is set in

A122

[Analog In Loss].

Values

Default:

0.0 Secs

Min/Max:

0.0/20.0 Secs

Display:

0.1 Secs

A166 [Analog In Filter]

Sets level of additional filtering of the analog input signals. A higher number increases filtering and
decreases bandwidth. Each setting doubles the applied filtering (1 = 2x filter, 2 = 4x filter, etc...). No
additional filtering is applied when set to “0”.

Values

Default:

0

Min/Max:

0/14

Display:

1

A167 [PID Invert Error]

When set to “Inverted”, changes the sign of the PID error. This causes an increase in the drive output
frequency with PID Feedback greater than PID Setpoint, and a decrease in drive output frequency
with PID Feedback less than PID Setpoint.

Options

0 “Not Inverted” (Default)

1 “Inverted”

22B-UM001.book Page 44 Wednesday, January 22, 2014 11:04 AM