3-42

Programming and Parameters

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual
Publication 22B-UM001H-EN-E

Advanced Program Group

(continued)

A150 [Stp Logic Time 0]
A151 [Stp Logic Time 1]
A152 [Stp Logic Time 2]
A153 [Stp Logic Time 3]
A154 [Stp Logic Time 4]
A155 [Stp Logic Time 5]
A156 [Stp Logic Time 6]
A157 [Stp Logic Time 7]

Related Parameter(s):

P038

,

A055

,

A058

,

A061

,

A070

-

A077

,

A140

-

A147

Sets the time to remain in each step if the corresponding StpLogic command word is set to “Step after
Time”.

Values

Default:

30.0 Secs

Min/Max:

0.0/999.9 Secs

Display:

0.1 Secs

A160 [EM Brk Off Delay]

Related Parameter(s):

P037

Sets the time the drive remains at minimum frequency before the relay or an opto output is energized
and the drive ramps to the commanded frequency.
The relay or opto output is typically connected to a user-supplied electromechanical brake coil relay.
Set

P037

[Stop Mode] to 8 “Ramp+EM B,CF” or 9 “Ramp+EM Brk” to enable the electromechanical

brake option.
Set

A055

[Relay Out Sel],

A058

or

A061

[Opto Outx Sel] to 22 “EM Brk Cntrl” to control brake

operation.
Values

Default:

2.00 Secs

Min/Max:

0.01/10.00 Secs

Display:

0.01 Secs

Frequency

Time

Minimum Freq

A160 [EM Brk Off Delay]

A161 [EM Brk On Delay]

Stop

Commanded

Start

Commanded

EM Brk

De-Energized (On)

Drive Stops

EM Brk
Energized (Off)

Ramp Accel

Ramp Decel

22B-UM001.book Page 42 Wednesday, January 22, 2014 11:04 AM