Supplemental drive information a-5 – Rockwell Automation 22B PowerFlex 40 FRN 1.xx - 6.xx User Manual

Page 105

Advertising
background image

Supplemental Drive Information

A-5

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual

Publication 22B-UM001H-EN-E

PowerFlex 40 Estimated Watts Loss (Rated Load, Speed & PWM)

Voltage

kW (HP)

External Watts

Internal Watts

Total Watts Loss

100–120V

0.4 (0.5)
0.75 (1.0)
1.1 (1.5)

22
40
58

18
20
22

40
60
80

200–240V

0.4 (0.5)
0.75 (1.0)
1.1 (2.0)
2.2 (3.0)
3.7 (5.0)
5.5 (7.5)
7.5 (10)

22
40
63
100
150
200
265

18
20
22
25
30
35
40

40
60
85
125
180
235
305

380–480V

0.4 (0.5)
0.75 (1.0)
1.1 (2.0)
2.2 (3.0)
3.7 (5.0)
5.5 (7.5)
7.5 (10)
11 (15)

17
30
48
75
135
140
175
260

18
20
22
25
25
35
35
40

35
50
70
100
160
175
210
300

460–600V

0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
4.0 (5.0)
5.5 (7.5)
7.5 (10)
11 (15)

30
48
75
135
140
175
260

20
22
25
25
35
35
40

50
70
100
160
175
210
300

22B-UM001.book Page 5 Wednesday, January 22, 2014 11:04 AM