PID Set Up

F-7

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual

Publication 22B-UM001H-EN-E

PID Preload

The value set in A139 [PID Preload], in Hertz, will be pre-loaded into
the integral component of the PID at any start or enable. This will cause
the drive’s frequency command to initially jump to that preload
frequency, and the PID loop starts regulating from there.

PID Limits

A130 [PID Trim Hi] and A131 [PID Trim Lo] are used to limit the PID
output and are only used in trim mode. [PID Trim Hi] sets the maximum
frequency for the PID output in trim mode. [PID Trim Lo] sets the
reverse frequency limit for the PID output in trim mode. Note that when
the PID reaches the Hi or Lo limit, the PID regulator stops integrating so
that windup does not occur.

PID Enabled

Freq Cmd

PID Output

PID Pre-load Value

PID Pre-load Value > 0