A084, Advanced program group, Continued) – Rockwell Automation 22B PowerFlex 40 FRN 1.xx - 6.xx User Manual

Page 72: A084 [boost select

Advertising
background image

3-26

Programming and Parameters

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual
Publication 22B-UM001H-EN-E

Advanced Program Group

(continued)

A084 [Boost Select]

Related Parameter(s):

d004

,

P031

,

P032

,

A085

,

A086

,

A087

,

A125

Sets the boost voltage (% of

P031

[Motor NP Volts]) and redefines the Volts per Hz curve.

Active when A125 [Torque Perf Mode] = 0 “V/Hz”.
Drive may add additional voltage unless Option 5 is selected.

Options

0 “Custom V/Hz”

1 “30.0, VT”

Variable Torque (Typical fan/pump curves.)

2 “35.0, VT”

3 “40.0, VT”

4 “45.0, VT”

5 “0.0 no IR”

Constant Torque

6 “0.0”

7 “2.5, CT”

[Default for
4.0, 5.5, 7.5 & 11 kW
(5.0, 7.5, 10 & 15 HP)
Drives]

8 “5.0, CT” (Default)

9 “7.5, CT”

10 “10.0, CT”

11 “12.5, CT”

12 “15.0, CT”

13 “17.5, CT”

14 “20.0, CT”

% P032 [Motor NP Hertz]

% P031 [Motor NP Volts]

100

50

1/2 [Motor NP Volts]

1/2

[Motor NP Hertz]

4
3
2
1

0

50

100

Settings

5-14

22B-UM001.book Page 26 Wednesday, January 22, 2014 11:04 AM

Advertising