Programming and Parameters

3-33

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual

Publication 22B-UM001H-EN-E

Advanced Program Group

(continued)

A109 [Anlg Out Setpt]

Related Parameter(s):

A065

When A065 [Analog Out Sel] is set to option 18, 19 or 20, this parameter sets the percentage of
analog output desired.

Values

Default:

0.0%

Min/Max:

0.0/100.0%

Display:

0.1%

A110 [Anlg In 0-10V Lo]

Related Parameter(s):

d020

,

P034

,

P038

,

A122

Sets the analog input level that corresponds to P034 [Minimum Freq] if a 0-10V input is used by P038
[Speed Reference].
Analog inversion can be accomplished by setting this value larger than A111 [Anlg In 0-10V Hi].

Values

Default:

0.0%

Min/Max:

0.0/100.0%

Display:

0.1%

0

P035 [Maximum Freq]

P034 [Minimum Freq]

A110 [Anlg In 0-10V Lo]

A111 [Anlg In 0-10V Hi]

0

Speed Reference

A111 [Anlg In 0-10V Hi]

Related Parameter(s):

d020

,

P035

,

P038

,

A122

,

A123

Sets the analog input level that corresponds to P035 [Maximum Freq] if a 0-10V input is used by P038
[Speed Reference].
Analog inversion can be accomplished by setting this value smaller than A110 [Anlg In 0-10V Lo].

Values

Default:

100.0%

Min/Max:

0.0/100.0%

Display:

0.1%

A112 [Anlg In4-20mA Lo]

Related Parameter(s):

d021

,

P034

,

P038

Sets the analog input level that corresponds to P034 [Minimum Freq] if a 4-20mA input is used by

P038

[Speed Reference].

Analog inversion can be accomplished by setting this value larger than A113 [Anlg In4-20mA Hi].

Values

Default:

0.0%

Min/Max:

0.0/100.0%

Display:

0.1%