A055, Advanced program group, Continued) – Rockwell Automation 22B PowerFlex 40 FRN 1.xx - 6.xx User Manual

Page 62

Advertising
background image

3-16

Programming and Parameters

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual
Publication 22B-UM001H-EN-E

Advanced Program Group

(continued)

A055 [Relay Out Sel]

Related Parameter(s):

P033

,

A056

,

A092

,

A140

-

A147

,

A150

-

A157

,

A160

,

A161

Sets the condition that changes the state of the output relay contacts.

Options

0 “Ready/Fault”

(Default)

Relay changes state when power is applied. This indicates
that the drive is ready for operation. Relay returns drive to
shelf state when power is removed or a fault occurs.

1 “At Frequency”

Drive reaches commanded frequency.

2 “MotorRunning”

Motor is receiving power from the drive.

3 “Reverse”

Drive is commanded to run in reverse direction.

4 “Motor Overld”

Motor overload condition exists.

5 “Ramp Reg”

Ramp regulator is modifying the programmed accel/decel
times to avoid an overcurrent or overvoltage fault from
occurring.

6 “Above Freq”

Drive exceeds the frequency (Hz) value set in

A056

[Relay

Out Level].

Use A056 to set threshold.

7 “Above Cur”

Drive exceeds the current (% Amps) value set in

A056

[Relay Out Level].

Use A056 to set threshold.

Important: Value for

A056

[Relay Out Level] must be entered

in percent of drive rated output current.

8 “Above DCVolt”

Drive exceeds the DC bus voltage value set in

A056

[Relay Out Level].

Use A056 to set threshold.

9 “Retries Exst”

Value set in

A092

[Auto Rstrt Tries] is exceeded.

10 “Above Anlg V”

Analog input voltage (I/O Terminal 13) exceeds the value
set in

A056

[Relay Out Level].

Do not use if

A123

[10V Bipolar Enbl] is set to 1 “Bi-Polar In”.

This parameter setting can also be used to indicate a PTC
trip point when the input (I/O Terminal 13) is wired to a
PTC and external resistor.

Use A056 to set threshold.

11 “Logic In 1”

An input is programmed as “Logic In 1” and is active.

12 “Logic In 2”

An input is programmed as “Logic In 2” and is active.

13 “Logic 1 & 2”

Both Logic inputs are programmed and active.

14 “Logic 1 or 2”

One or both Logic inputs are programmed and one or both is
active.

15 “StpLogic Out”

Drive enters StepLogic step with Digit 3 of Command Word
(

A140

-

A147

) set to enable StepLogic output.

16 “Timer Out”

Timer has reached value set in

A056

[Relay Out Level].

Use A056 to set threshold.

17 “Counter Out”

Counter has reached value set in

A056

[Relay Out Level].

Use A056 to set threshold.

18 “Above PF Ang”

Power Factor angle has exceeded the value set in

A056

[Relay Out Level].

Use A056 to set threshold.

22B-UM001.book Page 16 Wednesday, January 22, 2014 11:04 AM