Common symptoms and corrective actions – Rockwell Automation 22B PowerFlex 40 FRN 1.xx - 6.xx User Manual

Page 97

Advertising
background image

Troubleshooting

4-5

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual

Publication 22B-UM001H-EN-E

Motor does not Start.

F100 Parameter

Checksum

The checksum read from the
board does not match the
checksum calculated.

Set

P041

[Reset To Defalts] to

option 1 “Reset Defaults”.

F122 I/O Board Fail

Failure has been detected in the
drive control and I/O section.

1. Cycle power.
2. Replace drive if fault cannot be

cleared.

(1)

See

page 4-1

for a description of fault types.

No.

Fault

Ty

p

e

(1

)

Description

Action

Common Symptoms and Corrective Actions

Cause(s)

Indication

Corrective Action

No output voltage to the motor.

None

Check the power circuit.

Check the supply voltage.

Check all fuses and disconnects.

Check the motor.

Verify that the motor is
connected properly.

Check the control input signals.

Verify that a Start signal is
present. If 2-Wire control is used,
verify that either the Run
Forward or Run Reverse signal
is active, but not both.

Verify that I/O Terminal 01 is
active.

Verify that

P036

[Start Source]

matches your configuration.

Verify that

A095

[Reverse

Disable] is not prohibiting
movement.

Improper boost setting at initial
start-up.

None

Set

A084

[Boost Select] to option 2

“35.0, VT”.

Drive is Faulted

Flashing red status light

Clear fault.

Press Stop

Cycle power

Set

A100

[Fault Clear] to option 1

“Clear Faults”.

Cycle digital input if

A051

-

A054

[Digital Inx Sel] is set to option 7
“Clear Fault”.

22B-UM001.book Page 5 Wednesday, January 22, 2014 11:04 AM