Starting Your Processor

Chapter 5

5-20

Using the 1771ĆSIM Module

The Switch/Indicator module is compatible with any 1771 I/O chassis. It
has 8 switches to simulate 8 inputs and it has 8 LED’s to indicate when an
addressed output is active. It requires no external power. See
publication 1771-2.106 for more information.

ATTENTION: Use only trained personnel to conduct this test.
Have a trained person at appropriate emergency stop switches to
de-energize output devices that could cause hazardous
operation.

To test your input devices, do the following:

ATTENTION: Do not reach into a machine to actuate a switch
since unexpected machine motion can occur. Use a wooden
stick or other nonconductive device to guard against electrical
shock. Failure to observe this warning may injure personnel.

1.

Connect the industrial terminal to your processor (see chapter 4).

2.

Select the TEST mode of operation.

3.

Use an examine-on address corresponding to your input device
address. Use an energize-output address that is an internal storage
bit. For example, enter a rung similar to this one:

111

14

200

00

4.

Manually turn on one input device and observe that the input
instruction is intensified and the input module’s status indicator
lights. If both do, repeat this procedure for another input device.
Continue until all devices are tested.

Testing Input Devices