Sequencers

Chapter 21

21-4

Figure 21.4

Sequencer Instructions

Key Sequence

1770ĆT3 Display

Instruction Notes

SEQ 0

EN

SEQUENCER OUTPUT

COUNTER ADDR:
CURRENT STEP:
SEQ LENGTH:
WORDS PER STEP:
FILE:

001

1

110

DN

MASK:

010

OUTPUT WORDS

2:

3:

4:

030

17

030

15

030

001

110-

010-

1: 010

Output instruction

Increments, then transfers data.

Same data transferred each scan that the rung is true.

Counter is indexed by the instruction.

Unused output bits can be masked.

Requires 5-8 words of your program.

SEQ 1

SEQUENCER INPUT

COUNTER ADDR:
CURRENT STEP:
SEQ LENGTH:
WORDS PER STEP:
FILE:

001

1

110

MASK:

010

INPUT WORDS

2:

3:

4:

030

000

110-

010-

1: 010

Input instruction.

Compares input data with current step for equality.

Counter must be externally indexed by a counter instruction

within your program.

Unused input bits can be masked.

Requires 5-8 words of your program.

SEQ 2

EN

SEQUENCER LOAD

COUNTER ADDR:
CURRENT STEP:
SEQ LENGTH:
WORDS PER STEP:
FILE:

1

DN

LOAD WORDS

1:

2:

3:

4:

030

17

030

15

110

110-

010

001

030

000

Output instruction.

Increments, then loads data.

Counter is indexed by the instruction.

Does not mask.

Requires 4-7 words of your program.

Important: Numbers shown are default values. Numbers in shaded areas must be replaced by user-entered values. The number of default

address digits displayed (3 or 4) will depend on the size of the data table.

Here is an explanation of each value:

This Value:

Stores the:

Counter Address

Address of the instruction in the accumulated value area of

the data table

Position

Position in the sequencer table (accumulated value of counter)

Seq Length

Number of steps (preset value of the counter)

Words per Step

Width of the sequencer table

File

Starting address of the source file

Mask

Starting address of the mask file

Word Address

Address of the source word or destination word outside of the file

Output Words

Words controlled by the instruction

Load Words

Words fetched by the instruction

Input Words

Words monitored by the instruction