Timers and Counters

Chapter 11

11-3

When the timer on delay rung condition becomes:

True

Timer cycle begins.
Timer increments its AC value.
Bit 15 is set when AC=PR and the timer stops timing.
Bit 17 is set.

False

Accumulated value resets to 000.
Bits 15 and 17 are reset.

The accumulated value and status bits are also reset when the Mode Select
Switch is turned from the PROG position to RUN/PROGRAM or RUN.

The Timer Off Delay instruction is programmed as an output instruction.

010

00

TOF

030

1.0

PR 150

AC 000

When the timer off delay rung condition becomes:

True

Bit 15 is set.
Bit 17 is set.
Accumulated value resets to 000.

False

Timer cycle begins.
Timer increments its AC value.
Bit 15 resets when the AC=PR and the timer stops timing.
Bit 17 is reset.

Keystrokes

Enter a Timer On or a Timer Off Delay instruction by performing the
following steps.

1.

Press either -(TON)- or -(TOF)-.

2.

Enter <address>.

Timer Off Delay