EAF

Process Control Instructions

Chapter 16

16-9

Table 16.C

Control Word 02 Bit Descriptions: Status and SIgn Bits

00

- K

I

x10 (Set by User)

Do not move decimal = 0

Move decimal to right = 1

01

- K

P

/10 (Set by User)

Do not move decimal = 0

Move decimal = 1

02

- Feedforward/Bias Sign (Set by User)

Pos = 0

Neg = 1

03

- Maximum Scaling Sign (Set by User)

Pos = 0

Neg = 1

04

- Minimum Scaling Sign (Set by User)

Pos = 0

Neg = 1

05

- Set Point Sign (Set by User)

Pos = 0

Neg = 1

06

- Process Variable Sign (Set by Instruction)

Pos = 0

Neg = 1

1

07

- Error Sign (Set by Instruction)

Pos = 0

Neg = 1

1

10

- Resume Control From Last State

Disabled - on first scan, a new CO is calculated

Enabled = on first scan, the accumulated integral value is

backĆcalculated from the last CO value

2

11

- Bumpless Transfer With Proportional Controllers

0 = no adjustment to Bias

1 = bumpless manual to auto mode by adjusting Bias

3

Do not change these values. They are set by the PID function.

This bit should only be set after the PID program has been run to obtain a valid last CO value

Do not change while the processor is operating.

1