EAF

Process Control Instructions

Chapter 16

16-19

If you are using an 1771-IFE, -IL, -IR or -IXE module, place all module
configuration rungs except rung 2 in the main program. Place rung 2 in the
subroutine. Figure 16.5 shows what the modified STI block transfer looks
like. Please consult the module’s user manual for specific Block Transfer
programming requirements.

Figure 16.5

Initialization Rung

EN

BLOCK XFER READ

DATA ADDR:

MODULE ADDR:

BLOCK LENGTH:

FILE:

0030

100

20

0223

077

Storage

Alternate

Power

Storage

Up

Bit A

Block Transfer Read

Scan Bit

Bit B

Rung 1

Program a Get instruction as the first instruction of the
first rung to indicate that this is a selectable timed
interrupt. The time base is specified by the value in the
Get instruction, in this case, 50 ms.

Bit 077/00 enables the “alternate Scan” PID routines every
other scan. It goes on for one scan and off for the next scan

Rung 2

The BTR instruction executes every other scan.

Rung 3

The Immediate Output Update forces completion of the
BTR instruction.

Rungs

The first four PID instructions grouped with the first

4 7

output module.

Rung 8

The BTW for the first 4 PID instructions. The PIDs and the
BTW execute on the same scan.

Rung 9

IOT to force completion of the block transfer.

Rungs

The second four PID instructions grouped with the second

10 15

output module block transfer write and the IOT
instructions. The PIDs and the BTW execute on the
same scan.