18ć11, Block transfer write – Rockwell Automation 1772-L8_LW_LWP_LX_LXP,D17726.5.8 User Manual User Manual

Page 276

Advertising
background image

Block Transfer

Chapter 18

18-11

A block transfer writes data from the processor’s output image table to an
I/O module in one scan.

Programmed as an output instruction.
Block length depends on the type of module you are using.
Request for transfer is made in the program scan.
I/O scan is interrupted for the transfer.
Done bit remains on for one scan after a valid transfer.
Request requires two words of the data table.

Keystrokes
Enter a block transfer write (like this example) by performing the
following steps.

Block Transfer 0 appears in the lower left corner of the screen, above the
processor’s current programming mode.

BLOCK

XFER

0

EN

BLOCK X FER WRITE
DATA ADDR:
MODULE ADDR:
BLOCK LENGTH:
FILE:

030
100

01

110- 110

DN

110

06

010

06

Note that the words BLOCK TRANSFER WRITE are flashing.

Insert the following values. The cursor moves automatically through the
block transfer write instruction. The values are:

DATA ADDRESS

031

MODULE ADDRESS

130

BLOCK LENGTH

05

FILE

060Ć064

The instruction should look like this:

EN

BLOCK X FER READ
DATA ADDR:
MODULE ADDR:
BLOCK LENGTH:
FILE:

031
130

05

060- 064

DN

113

06

013

06

The Block Transfer enable bit is 01006; the done bit is 11006.

Block Transfer Write

Advertising