Rockwell Automation 1772-L8_LW_LWP_LX_LXP,D17726.5.8 User Manual User Manual

Page 291

Advertising
background image

Block Transfer

Chapter 18

18-26

Setting the Number of Words to Transfer

Each block transfer module has a default value that specifies the maximum
number of words that can be transferred. Either the default value or some
lesser value can be selected. For bi-directional block transfers, use the
default value of the module. The default value varies from one kind of
module to another, consult the appropriate module documentation
for specifics.

When you what fewer words, set the number of words to be transferred by
programming support rungs. The number of words is stored in the upper
or lower Output Image Table byte that corresponds to the module’s
location in the I/O rack. The appropriate bits must be set On to specify a
binary value that equals the number of words to transfer (Figure 18.13).
These bits can be set On by programming unconditional Output Energize
or Output Latch instructions.

Figure 18.13

Setting the Number of Transfer Words

10385-I

0

0

5

Block Transfer Data

030

050

054

114

130

0

1

4

1

1

014

Bit 6 of 7 if a successful

block transfer occurred.

1

1 0 0 0 0

0

1 0 1

# Words

To Transfer

Bit Pattern

7 6 5 4 3 2 1 0

Default

1

2

3

4
5

62

63
64

0 0 0 0 0 0
0 0 0 0 0 1
0 0 0 0 1 0
0 0 0 0 1 1

0 0 0 1 0 0
0 0 0 1 0 1

1 1 1 1 1 0

1

0 0 0 0 0 0

1 1 1 1 1

Read 5 words from module