Figure 4.10

Ground Bus Connections

10309-I

ground bus

ground lug

ground bus mounting

equipment grounding

conductors

grounding electrode conductor

to grounding electrode system

Figure 4.11

Details of Ground Connection at Enclosure Wall

10310-I

enclosure wall (inside)

ground lug

scrape paint on both sides

nut

star washer

equipment grounding

conductor

enclosure wall (outside)

star washer

bolt

Connect an equipment grounding conductor directly from each chassis to
an individual bolt on the ground bus (Figure 4.12). For those chassis with
a ground stud, use the ground stud for this connection. For those chassis
with no ground stud, use a mounting bolt.