Chapter 25

25-9

This application illustrates the program control instructions, master control
reset (MCR) and zone control last state (ZCL) (Figure 25.8).

Figure 25.8

Program Control

110

17

MCR

ZCL

110

16

15

011

MCR

Master Control Reset

110

17

ZCL

110

16

15

011

Zone Control Last State

Before you program these two instructions, you must think about how you
would want outputs to react when you change the process or operation.

Using the MCR instruction, rung logic shows:

If bit 110/17 is false, then bit 011/15 is energized if 110/16 is set. This

is normal operation.

If bit 110/17 is true, then bit 011/15 is reset regardless of the state of

110/16. All outputs within an MCR zone are reset when the zone is
disabled (start fence is false).

Using the ZCL instruction, rung logic shows:

If bit 110/17 is false, then bit 011/15 is energized if 110/16 is set. This

is normal operation.

If address 110/17 is true, then bit 011/15 is left in its last state regardless

of the state of 110/16. All outputs within a ZCL zone are left in their
last state when the zone is disabled (start fence is false).

Program Control