Rockwell Automation 1772-L8_LW_LWP_LX_LXP,D17726.5.8 User Manual User Manual

Page 314

Advertising
background image

Bit Shift Registers

Chapter 20

20-4

A display represented by Figure 20.2 shows the format of a Bit Shift Left.

Figure 20.2

Bit Shift Left Format

EN

BIT SHIFT LEFT

COUNTER ADDR:
NUMBER OF BITS:
FILE:
INPUT:
OUTPUT:

001

110-110

010/00
010/00

DN

020

10

030

17

030

15

030

Numbers shown are default values. The number of default address digits initially displayed, 3, 4,

or 5 will depend on the size of the data table. Initially displayed default values are governed by the

I/O rack configuration.

This Value:

Stores This:

Counter Address

Address of the instruction in the timer/counter area of the data

table. It represents the accumulated value of the instruction.

Number of Bits

Number of bits in the file.

File

Starting address of the file.

Input

Address of the input bit.

Output

Address of the output bit.

After you enter the following data, the instruction should look
like Figure 20.3.

COUNTER ADDR

200

NUMBER OF BITS

128

FILE

The bit shift register starts and ends at

words 400 and 407 respectively.

INPUT

The input bit is bit 17 of word 130.

OUTPUT

The output bit is bit 00 of word 420.

Figure 20.3

Bit Shift Left Example Rung

EN

BIT SHIFT LEFT

COUNTER ADDR:
NUMBER OF BITS:
FILE:
INPUT:
OUTPUT:

128

400-407

130/17
420/00

DN

020

10

200

17

200

15

200

See chapter 19 for the procedure for using the data monitor. Note that
bit 00 is the right side bit on the file display and bit 17 is on the left.