Figure 4.3

Power Supplies and Input Circuits Receiving Power through a

Separate Transformer

L1

L2

L3

1FU

2FU

3FU

H

L1

L2

L3

H

1

4

H

3

H

2

X

1

X

2

H

H

1

4

H

3

H

2

X

1

X

2

10302-I

to motor starters

stepĆdown

transformer

incoming ac

disc

to power supplies

and input circuits

isolation/constantĆvoltage

transformer

to output circuits

Ground Connection

When bringing ac power into the enclosure, do not connect its raceway
through an equipment-grounding conductor to the ground bus on the
back-panel. The raceway should be grounded elsewhere. Connecting the
raceway to the ground bus would cause a ground loop.