Bit Shift Registers

Chapter 20

20-6

Upon false-to-true rung transition, input bit B from a particular input word
will be inserted into the last bit of the bit shift register. In Figure 20.4, bit
128 moves right and displaces bit 127; bit 127 displaces bit 126. Each bit
displaces the one on its right until the first bit in the word, 113, is reached.
Bit 113 then displaces bit 112 in the previous word (in this example, bit
406/17). This bumping procedure continues throughout the queue until bit
1 is ejected from the file into output bit A.

If the bit shift register of Figure 20.4 had been 123 bits long it would have
input data into bit 12 of word 407. In this case the bits to the left of bit 12
in word 407 would be unused and cannot be used for any other purpose. A
Bit Shift Right will shift the on or off status of input bit B directly into bit
123 as shown by the dotted line.

The instruction operates in the complete mode. The status of the input bit
is shifted into the last bit in the register and the status of the first bit in the
register is shifted into the output bit in one scan.

Here are some characteristics of the Bit Shift Right instruction:

Programmed as an output instruction

Key sequence [Shift] [Reg] [1] [3]

The counter is internally indexed and externally controlled by the ladder

diagram logic in your program.

Operates in complete mode

Requires 6 words of your program

Programming Bit Shift Right Instruction

ATTENTION: The counter address specified for the Bit Shift
Right instruction should be reserved for that instruction only.
Do not manipulate the counter preset or accumulated values.
Inadvertent change to these values could result in hazardous or
unpredictable machine operation or a run time error. Damage to
equipment and/or personal injury could result.

Advertising