EAF

Process Control Instructions

Chapter 16

16-23

De-scaling is necessary to force the PID input range to 0 to 4095 when
using an input module that does not return this range. A thermocouple
input module is a good example. It returns a scaled temperature range,
typically -300

°

to +1200

°

Fahrenheit. When specifying the input range for

de-scaling, specify the maximum range that your process will actually see.
For example, if your thermocouple input range is -300

°

to +1000

°

C but

your process could only possibly experience 25

°

to +550

°

C, then use the

latter range in the de-scaling equation. This improves the resolution for the
PID instruction and results in better system control.

Figure 16.8

DeĆScaling Inputs

(

(

(

Processor

Scaling

0Ć4095

PID

Instr.

DeĆscaling

Equation

Operator

Interface

SP

PV

C0

0Ć4095

Analog

Signal

Analog

Output

25Ć550

o

C

Analog Signal

Heater

Thermocouple

Thermocouple

Input

Smax

2

= 550

o

C

Smin

2

= 25

o

C

Smax

1

= 4095

Smin

1

= 0

10373-I

Example: If measuring a full scale temperature range of 25

°

to 550

°

C,

enter 25 for the minimum scaling value and 550 for the maximum
scaling value.

M

2

+ (M

1

* Smin

1

)

(Smax

2

* Smin

2

)

(Smax

1

* Smin

1

)

) Smin

2

where:

M

=

Measured value

Smin =

Minimum Scaling Value

Smax =

Maximum Scaling Value

DeĆScaling Inputs