Repeat steps 2 and 3 until you wire the appropriate I/O devices to the
field wiring arm.

10618ĆI

5.

Connect the drain wire to ground.

6.

Gather all wires and neatly bundle them using tie wraps.

7.

Label all wires with a 5-digit I/O address code at each wire
connection. Chapter 7 describes I/O addressing.

MultiĆConductor Shielded Cable

Intelligent and low-voltage dc discrete I/O modules require shielded cables
that help to reduce the effects of electrical noise coupling. Ground a shield
at one end only as specified in the appropriate publication for the product.
A shield grounded at both ends may form a ground loop that can introduce
objectionable ground currents resulting in faulty operation of the
programmable controller.

Avoid breaking shields at junction boxes. If you do break a shield at a
junction box, make sure that the junction box contains only low-level
conductors. Also, do not strip the shield back any farther than necessary to
make a connection.