14ć17, 10 to the x – Rockwell Automation 1772-L8_LW_LWP_LX_LXP,D17726.5.8 User Manual User Manual

Page 189

Advertising
background image

EAF Math Instructions

Chapter 14

14-17

Figure 14.16

EAF Square Root Format in the Data Table After Execution

17 16 15 14 10 7 4 3

Data

Address

0

Result

Address

10356-I

13

X

0

040

041

042

043

060

061

062

063

0

0

0

0

0

0

0

S

0

0

0

0

0

0

0

0

1

4

4

0

0

0

0

0

1

2

Operand A

Result

The 10 to the x function finds the value of 10

x

= y. The Operand and

Result words have the format:

x = exponent of 10 (maximum value = 5.999 999)
y = resultant number (maximum of 6 digits)

10

+/–x . xxx xxx

= yyy yyy . yyy yyy

Enter an EAF rung like that shown in Figure 14.17.

Figure 14.17

EAF Power of 10 Function Input and Display Rung

060

EXECUTE AUX

FUNCTION

FUNCTION NUMBER:

DATA ADDR:

RESULT ADDR:

37

040

060

G

061

243

G

062

221

G

063

000

G

040

G

041

002

G

042

386

G

043

000

G

000

000

Enter values for the operand. You can enter these values from the
keyboard of your 1770-T3 terminal or through ladder diagram functions.
Entry of an operand (exponent of 10) of 000 002 . 386 000 yields an
exponential value of 000 243 . 221 000. Figure 14.18 shows how it is
stored in the data table.

10 to the X

Advertising