Installing Your

Programmable Controller

Chapter 4

4-23

Table 4.C

Set Switches 1, 4, 5 and 8

If you want:

Then set:

And

Outputs to remain in their last state when a fault

(red LED in ON) is detected

Outputs to deĆenergize when a fault (red LED is

ON) is detected

1

1

Switch 1 ON

Switch 1 OFF

--

--

2Ćslot addressing
1Ćslot addressing
1/2Ćslot addressing

2

3

4

Switch 4 OFF

Switch 4 OFF

Switch 4 ON

Switch 5 OFF

Switch 5 ON

Switch 5 ON

RAM memory protect disabled

RAM memory protect enabled

5

Switch 8 OFF

Switch 8 ON

--

Last state switch only on PLCĆ2/16 and Ć2/17 series C or later, and PLCĆ2/02 series A or later.

1

2

3

4

5

When using 2Ćslot addressing and 8Ćpt. I/O modules: a 16Ćslot chassis equals one rack which can

address 128 I/O. See chapters 5 and 7.
When using 1Ćslot addressing and 16Ćpt. I/O modules: a 16Ćslot chassis equals two racks which can

address 256 I/O. See chapters 5 and 7.
When using 1/2Ćslot addressing and 16Ćpt. I/O modules: a 16Ćslot chassis can address four racks which

equals 512 I/O. See chapters 5 and 7.
When memory protect is enabled, you can only change the status and value of the bits in the first 128

words (word addresses up to 177

8

) of the data table.