Figure 4.16

Place Each I/O Module into its Corresponding Keyed Slot in the

I/O Chassis

20213

I/O module

locking bar

card guides

corresponding keyed slot

ATTENTION: Do not force and I/O module into a backplane
connector. Forcing an I/O module can damage the backplane
connector or the I/O module.

Calculate the total current requirement for all installed modules to ensure
that the sum does not exceed the limit of the I/O chassis’ power supply.
The 1772-LWP, -LXP, and -LZP processor provides 4A to power the I/O
modules. If you need additional power, you can choose either a 1771-P3
or 177-P4 power supply module to parallel to the 1772-LWP, -LXP, -LZP:

Catalog Number

Input Voltage

Current to the

Backplane

1771ĆP3

120V ac

3A

1771ĆP4

120V ac

8A

1771ĆP5

24V ac

8A

1771ĆP7

120/220V ac

16A