Installing Your

Programmable Controller

Chapter 4

4-2

A well-planned layout is essential for the installation of your processor.
You should consider the following factors:

location
environment
mechanical

protection

conductor

categories

raceway

layout

power

distribution

surge

suppression

Location

Determining the proper location should be your primary concern.
We specify:

This Characteristic:

Should Meet this Specification:

Operating temperature

0 to 60

o

C (32 to 140

o

F)

Storage temperature

Ć40 to 85

o

C (Ć40 to 185

o

F)

Relative humidity

5 to 95% (without condensation)

Environment

Separate the processor system from other equipment and plant walls to
allow for convection cooling. Convection cooling draws a vertical column
of air upward over the processor. Cooling air must not exceed 60

o

C

(140

o

F) at any point immediately below the processor. If the air

temperature does exceed 60

o

C, install:

fans inside the enclosure to bring in filtered air or recirculate internal

air, or

air conditioning/heat exchangers

Follow these guidelines when installing your processor system:

Allow six vertical inches above and below all processor components,

including other processors.

Allow four horizontal inches on the sides of each processor component.

When you use more than one processor in the same area, allow six
horizontal inches between each processor.

Allow two inches (vertical and horizontal) between the processor and

the wiring duct or terminal strips.

Mount the I/O chassis horizontally to allow convection cooling.

Planning Your

Processor System