SEQ

Sequencer

Chapter 21

21-21

ATTENTION: The counter address of the sequencer load
instruction should be reserved for that instruction. Do not
manipulate the counter accumulated or preset word. Changes to
these values could result in unexpected machine operation with
damage to equipment and injury to personnel.

You are now ready to program your sequencer load instruction.

The word SEQUENCER is displayed in the lower left corner of the screen.

SEQUENCER INPUT

COUNTER ADDR:
CURRENT STEP:
SEQ LENGTH:
WORDS PER STEP:
FILE:

001

1

110

INPUT WORDS

2:

3: 4:

030

001

110-

1: 010

EN

DN

17

15

030

030

2

Insert the following values. The cursor moves automatically throughout
the Sequencer Load instruction. The values are:

COUNTER ADDRESS 056
CURRENT STEP 008
SEQ LENGTH 012
WORDS PER STEP 4
FILE 510
LOAD WORDS 1: 110

2: 113
3: 012
4: 314

To continue, enter your data using the binary data monitor mode. You will
get your data from the worksheet (Figure 21.7). A filled-in block means a
1 should be inserted in the corresponding bit location.