Eć34, Timer instructions – Rockwell Automation 1772-L8_LW_LWP_LX_LXP,D17726.5.8 User Manual User Manual

Page 478

Advertising
background image

Quick Reference

Appendix E

E-34

Important: The timer word address, XXX, is assigned to the timer
accumulated areas of the data table. To determine which addresses are
valid accumulated areas, the third digit from the right must be an
even number.

The time base 1.0, 0.1 or 0.01 second. Preset values, YYY, and
accumulated values, ZZZ, can vary from 000-999.

Bit 15 is the timed bit.
Bit 17 is the enable bit.

The word address displayed will be 3 or 4 digits long depending on the
data table size. When entering the word address, use a leading zero
if necessary.

Key

Symbol

Instruction

Name

1770ĆT3

Display

Rung Conditions

Status Bits

-(TON)-

Timer On Delay

XXX

-(TON)-

TB

PR YYY

AC ZZZ

When the rung is true, the timer begins

to increment the accumulated value at a

rate specified by the time base.

When the rung is false, the timer resets

the accumulated value to 000.

When the rung is true and AC = PR:

bits 15 and 17 set

When the rung is false:

bits 15 and 17 reset

-(TOF)-

Timer Off Delay

XXX

-(TOF)-

TB

PR YYY

AC ZZZ

When the rung is true, the timer resets

the accumulated value to 000.

When the rung is false, the timer begins

to increment the accumulated value.

When the rung is true: bits 15, 17 are set

When the rung is false and AC = PR:

bits 15 and 17 reset

-(RTO)-

Retentive

Timer

-(RTO)-

TB

PR YYY

AC ZZZ

When the rung is true, the timer begins

to increment the accumulated value.

When false, the accumulated value

is retained.

When the rung is true and AC = PR:

bits 15 and 17 set

When the rung is false: bit 15 no action taken,

but bit 17 is reset

-(RTR)-

Retentive

Timer

XXX

-(RTR)-

PR YYY

AC ZZZ

XXX - Word address of the retentive

timer. It is resetting.

The preset and accumulated values are

automatically entered by the

industrial terminal.

When the rung is true,t he accumulated

value and status bits are reset.

When the rung is true: bits 15 and 17 are reset

When the rung is false: no action is taken

Timer Instructions