Chapter 5

5-13

Figure 5.10

Example of 1ĆSlot Addressing

01

23

45

67

01

23

45

67

13499

I/O group 1

address

1 1 1

input

rack

I/O group

I/O group 1

address

1 2 1

I/O group number

rack 1

rack 2

Using 32-Point I/O Modules
32-point I/O modules provide 32 input or 32 output terminals. 32-point
I/O modules use two full words in the input or output image table. In
1-slot addressing mode, 32-point modules must be placed in a
complimentary fashion; a 32-point input module must be next to any
output module and vice versa.

If 32-point modules are not placed in a complimentary fashion when in
1-slot addressing mode, the PROC RUN LED indicator will continuously
blink green and the processor will not operate.

Important: When addressing a block transfer module, it must be
addressed by the lowest group number that it occupies and at slot 0. For
example: a 2-slot block transfer module in rack 1, groups 2 and 3 (slots 3
and 4) would be addressed (by rack-group-slot) at location 120.